Standard Features
Double Aperture
Includes Zone LED Module and Printer
Single Aperture
• UL Listed (Tenth Edition) and FM Approval – PENDING
•  2 to 16 loop versions
• 400mA loop current
• 400 sub-address points per loop (800 per loop module)
• 4 programmable NACs; Class B or 2 Class A
• Multiple internal NAC synchronization protocols
• 10.25 A power supply options
• 3 programmable inputs and 5
programmable relay outputs
• 7 inch, full-color resistive touch screen
with intuitive user interface
• Up to 24 programmable soft “function keys”
• Up to 64 user login accounts
• Positive Alarm Sequence
• Pre-Signal
• Alarm Verification
• Drift Compensation
• CO Alarm
• Hard-wired fire and trouble routing inputs and outputs
• Modular and expandable electronics
• Option to “invert” inputs and outputs
• 5000 programmable cause and effects;
over 50,000 inputs and outputs
• Can be networked with programmable functionality
• Programming via USB or PC
• L@ti-View Graphical PC User Interface – coming soon!

Technical Specifications

2 to 16 LOOP (8 SLOT) ENCLOSURE
Size Standard Cabinet – 540mm (W) x 720mm (H) x 160mm (D)
21.3in (W) x 28.3in (H) x 6.3in (D)
Deep Cabinet – 540mm (W) x 720mm (H) x 212mm (D)
21.3in (W) x 28.3in (H) x 8.3in (D)
Construction Mild sheet steel enclosure, 1.5 mm
Cable Entry Knockouts Standard Cabinet – 38 top, 25 back, 2 per side, 2 bottom
Deep Cabinet – 50 top, 25 back, 2 per side, 2 bottom
Battery Capacity Standard Cabinet – Up to 28 Ah (Power Sonic PS-12280)
Deep Cabinet – Up to 40 Ah (Power Sonic PS-12400)

ALL MODELS

Finish Epoxy powder coated
Color Lid & Box Red (RAL3002) Gray (BS 00 A 05) Black (RAL9005)
Fascia Signal White (RAL9003)
Power supply voltage 120 V AC or 240 V AC
Power supply rating at 24V DC 5.25 A (charges up to 60 Ah)
10.25 A (charges up to 100 Ah)
Display Full-color 800 x 480 LCD with resistive touch screen and automatic backlight dimming.
Software zones 2000
Software groups 5000
Cause and Effects 5000
Event log 10,000 events, 1 second resolution. Filterable and printable.
Detection loops 2 – 16, added 2 at a time via dual loop panel module (S758)
Detection loop current 400 mA each
AUX 24V Output 2; each rated at 900 mA
NACs 4; each rated at 2.5 A. Max 5A combined output for all channels. Class B or 2 Class A.
Programmable Relay Outputs 5; 30 V DC 1 Amp
Programmable Inputs 3; designed to be activated by voltage-free contacts
Network Connection Optional network card provides communication for networking fire control panels
NAC Synchronization Internal Support of System Sensor, Wheelock, Gentex, and Amseco protocols
Printer (OPTIONAL) 40 column, front-loading thermal
Zone LED Indicators (OPTIONAL) Up to 3 banks of 48 (144) as standard

Based on 0 reviews

0.0 overall
0
0
0
0
0

Be the first to review “firenet Latitude 10 loop-Hochiki”

18 − 3 =

There are no reviews yet.

No more offers for this product!

General Inquiries

There are no inquiries yet.

Shopping Cart
0
Chat Now
Chat Now
Questions, doubts, issues? We're here to help you!
Connecting...
None of our operators are available at the moment. Please, try again later.
Our operators are busy. Please try again later
:
:
:
Have you got question? Write to us!
:
:
This chat session has ended
Was this conversation useful? Vote this chat session.
Good Bad